Induced Voltage Triple Frequency Generator
The triple frequency induced withstand voltage generator is designed to meet the requirements of GB1094.3—85, GB1207, and the regulations for preventive tests of electrical equipment — 1995 for triple frequency induced withstand voltage tests and partial discharge tests. The induced withstand voltage test for transformers and instrument transformers is an important test to verify that the product complies with national standards. The longitudinal insulation induction test of winding layers, turns, sections, and phase-to-phase insulation is an important item to assess whether the winding meets the requirements. To increase the test voltage without over-saturating the transformer or instrument transformer core, which would lead to excessive excitation current, the test frequency is generally increased.
Product Features
Simple operation, reliable performance, and can well meet the needs of induced withstand voltage tests for transformers and instrument transformers.
Product Parameters
1. Input voltage: three-phase 380V, 50Hz;
2. Output voltage: 50—500V max 750V, 150Hz; 100—1000V max 1500V, 150Hz;
3. Capacity: 1-1000KVA;
4. Waveform: sine wave, distortion less than 1;
5. Load characteristics: resistive, inductive, capacitive all applicable;
![]()