全自动Dielectric Loss Tester-扬州达瑞

Triple Frequency Power Generator

Published: 2019-08-21 10:02:52

Views: 2922

Category: Triple Frequency Generator

Product Description

Triple Frequency Power Generator



 The induced overvoltage withstand test of transformers and instrument transformers is an important test to verify whether the product meets national standards. The longitudinal insulation induction test of winding layers, turns, sections, and phases is an important item to verify whether the winding meets the requirements. In order to increase the test voltage of the winding without causing the transformer or instrument transformer core to saturate excessively and lead to excessive excitation current, the test frequency needs to be increased, generally to 100Hz-400Hz. There are multiple ways to obtain a 100Hz-400Hz power supply, among which the more applicable ones are: ① Three variable-frequency generator sets (100Hz-400Hz); ② Three single-phase transformers combined (150Hz), and the most convenient is the second method. The combination of three single-phase transformers: the primary side is star-connected, and the secondary side is open delta. When the core is not saturated, the main flux it produces must be a flat-topped wave. Since the flat-topped main flux contains a large component of third harmonic magnetic energy Φ3, and the third harmonic flux frequency f3=3f1, the main flux induces a third harmonic phase electromotive force. Because the primary side is star-connected and the secondary side is open delta, the core operates in a saturated state, and the no-load current I is a peaked wave. In addition to the fundamental wave, it also contains higher harmonics. Among the higher harmonics, the amplitude of I is larger. Since the secondary side is open, the three-phase fundamental components cancel each other out, leaving only the third harmonic output. The triple frequency power generator utilizes the saturation characteristics of the magnetic circuit to extract the third harmonic voltage, which has the largest component among harmonics, as the power supply for the generator. It is used for turn-to-turn, section-to-section, and layer-to-layer frequency doubling and voltage doubling tests on inductive coil-type electrical products such as transformers and instrument transformers, to assess the insulation strength and withstand voltage level of the coils.

Technical Parameters:

1. Working power supply: Three-phase AC 380V ±10% 50Hz

2. Rated capacity: 3KVA-30KVA (optional)

3. Input voltage: 380V 50Hz sine wave

4. Output voltage: 250V-1000V 150Hz waveform distortion ≤5%

5. Output capacity: 3kVA, 5kVA, 10kVA, 20kVA, 50kVA

6. No-load operation time ≤5 minutes

7. Load operation time: 40-60s



Model

Input Voltage (V)

Output Voltage (V)

Capacity (KVA)

SFQ-81-3/500

380

0-500

3

SFQ-81-5/500

380

0-500

5

SFQ-81-10/500

380

0-500

10

SFQ-81-15/500

380

0-500

15

SFQ-81-20/500

380

0-500

20

SFQ-81-5/1000

380

0-1000

5

SFQ-81-10/1000

380

0-1000

10

SFQ-81-20/1000

380

0-1000

20

SFQ-81-50/1000

380

0-1000

50




WeChat QR Code
💬
💬 Message

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us