Product Features
1. The reactors of the same voltage level and capacity are smaller in size and lighter in weight; under rated load, the temperature rise is small; using dry-type epoxy casting, with high mechanical strength, good electrical insulation performance, beautiful and reliable
2. The variable frequency power supply control box has large capacity margin; strong protection functions; good output waveform; good stability; with multiple working modes, easy operation; single-phase 220V or three-phase 380V input power supply universal, convenient for on-site power access
3. Flexible configuration. Different types of reactors can be optionally configured to meet different test object requirements, achieving multiple uses with one machine, high cost performance
Technical Indicators:
| Rated Output Voltage | 0~1000kV and below |
| Output Frequency | 30~300Hz |
| Resonant Voltage Waveform | Pure sine wave, waveform distortion rate ≤1.0% |
| Working System | Full power continuous working time 60min |
| Quality Factor | 30~90 |
| Frequency Adjustment Sensitivity | 0.1Hz |
| Instability | <0.05% |
| Working Power Supply | Single-phase 220V or three-phase 380V±10% |
| Power frequency 50Hz±5% |
Series Product Configuration and Applicable Scope:
| Product Model Name | Applicable Scope (AC withstand voltage test equipment for electrical equipment in substations of 10kV~500kV voltage levels, frequency 30~300Hz) | ||||
| Variable Frequency Source | Resonant Reactor | Excitation Transformer | Voltage Divider | Applicable Scope | |
| BPXZ-50/50/25 | 3kW | 25kV/1A two units (dry-type) |
3kVA (dry-type) |
50kV | 1000kVA and below 10kV power transformer 10kV switchgear, busbar, PT, CT, etc. 10kV (300mm2) cable ≤1.0km |
| BPXZ-108/108/27 | 5kW | 27kV/1A four units (dry-type) |
5kVA (dry-type) |
110kV | 31500kVA and below 35kV power transformer 35kV switchgear, busbar, PT, CT, etc. 10kV (300mm2) cable 2km 35kV (300mm2) cable 0.5km |
| BPXZ-200/200/50 | 10kW | 50kV/1A four units (dry-type) |
10kVA (dry-type) |
200kV | 50000kVA and below 110kV power transformer 110kV GIS, PT, CT, etc. (preventive test) 35kV (300mm2) cable ≤1.0km 10kV (300mm2) cable ≤2.0km |
| BPXZ-270/270/45 | 15kW | 45kV/1A six units (dry-type) |
15kVA (dry-type) |
300kV | 50000kVA and below 110kV power transformer 110kV GIS, PT, CT, etc. 35kV (300mm2) cable ≤1.2km 10kV (300mm2) cable ≤3.0km |
| BPXZ-800/400/50 | 30kW | 50kV/2A eight units (dry-type) 100kV/2A four units (oil-immersed) |
30kVA (dry-type) 30kVA (oil-immersed) |
400kV | 80000kVA and below 220kV power transformer 50000kVA and below 110kV power transformer 110kV/220kV GIS, PT, CT, etc. 35kV (300mm2) cable ≤2.0km 110kV (300mm2) cable ≤0.7km |
| BPXZ-1600/800/200 | 60kW | 200kV/2A four units (oil-immersed) |
60kVA (dry-type) |
800kV | 80000kVA and below 220kV power transformer 50000kVA and below 110kV power transformer 500kV GIS, PT, CT, etc. 220kV switchgear, GIS, PT, CT, etc. 110kV (400mm2) cable ≤1.5km 220kV (400mm2) cable ≤1.0km |