Program-controlled Ultra-low Frequency High Voltage Generator 

Dary Electric recommends for you:


Product Features of Program-controlled Ultra-low Frequency High Voltage Generator

  • Current, voltage, and waveform data are all sampled directly from the high-voltage side, ensuring data authenticity and accuracy.

  • Overvoltage protection: When the output exceeds the set voltage limit, the instrument will shut down for protection, with an action time of less than 20 milliseconds.

  • Overcurrent protection: Designed with dual protection on both high and low voltage sides; the high-voltage side can perform precise shutdown protection according to the set value.

  • When the current on the low-voltage side exceeds the rated current, shutdown protection will be triggered, with an action time of less than 20 milliseconds.

  • The high-voltage output protection resistor is designed inside the booster, so no external protection resistor is needed.

  • Due to the adoption of a closed-loop negative feedback control circuit for both high and low voltages, there is no capacitive rise effect in the output.




Product Parameters


  • Output frequency: 0.1Hz, 0.05Hz, 0.02Hz

  • Load capacity:

    • 0.1 Hz max 1.1F

    • 0.05 Hz max 2.2F

    • 0.02 Hz max 5.5F



  • Measurement accuracy: 3%

  • Voltage positive and negative peak error: ≤3%

  • Voltage waveform distortion: ≤5%

  • Operating conditions:

    • Indoor and outdoor;

    • Temperature: -10℃∽+40℃

    • Humidity: ≤85% RH



  • Power supply: AC 50Hz, 220V ±5%



Model Peak Voltage Measurement Range Weight Application
GDVLF-30/1.1 30kV
  • At 0.1Hz: ≤1.1μF
  • At 0.05Hz: ≤2.2μF
  • At 0.02Hz: ≤5.5μF
Controller: 4kg 
Booster: 25kg
For cables, motors, etc. with voltage up to 10kV and below
GDVLF-40/1.1 40kV
  • At 0.1Hz: ≤1.1μF
  • At 0.05Hz: ≤2.2μF
  • At 0.02Hz: ≤5.5μF
Controller: 5kg 
Booster: 25kg
For cables, generators, etc. with voltage up to 13.8kV and below
GDVLF-50/1.1 50kV
  • At 0.1Hz: ≤1.1μF
  • At 0.05Hz: ≤2.2μF
  • At 0.02Hz: ≤5.5μF
Controller: 6kg 
Booster: 25kg
For cables, generators, etc. with voltage up to 15.75kV and below
GDVLF-60/1.1 60kV
  • At 0.1Hz: ≤1.1μF
  • At 0.05Hz: ≤2.2μF
  • At 0.02Hz: ≤5.5μF
Controller: 6kg 
Booster: 45kg
For cables, generators, etc. with voltage up to 18kV and below
GDVLF-80/0.5 80kV
  • At 0.1Hz: ≤1.1μF
  • At 0.05Hz: ≤2.2μF
  • At 0.02Hz: ≤5.5μF
Controller: 7kg 
Two boosters: 65kg
For cables, generators, etc. with voltage up to 35kV and below



Note: The above information and technical parameters are compiled and released by Yangzhou Dary Electric Co., Ltd.
WeChat QR Code
💬
💬 Message

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us