Multifunctional Handheld Partial Discharge Online Detector
Darui Electric recommends for you:
ZCPD-100Z Multifunctional Handheld Partial Discharge Online Detector can be used with transient earth voltage (TEV) sensors, contact ultrasonic sensors, non-contact ultrasonic sensors, broadband current transformers, and UHF sensors for online detection of partial discharge in high-voltage equipment such as transformers, high-voltage switchgear, GIS, cable joints, and generators. ZCPD-100Z Multifunctional Handheld Partial Discharge Online Detector is easy to carry, quick to measure, and has strong anti-interference capability, making it convenient for on-site use.
Functional Features
1. ZCPD-100Z Multifunctional Handheld Partial Discharge Online Detector Shanghai Duanyi Electric uses transient earth voltage (TEV) combined with ultrasonic sensors to detect the magnitude of partial discharge in high-voltage switchgear. It combines contact and non-contact measurement (handheld ultrasonic receiving antenna) for both qualitative and quantitative analysis.
2. Uses broadband current transformers and contact ultrasonic sensors to detect the magnitude of partial discharge in transformers.
3. Uses contact ultrasonic and UHF sensors to detect the magnitude of partial discharge in GIS.
4. Uses broadband current transformers to detect the magnitude of partial discharge in cable joints.
5. For non-contact ultrasonic sensors, sound analysis can be performed through headphones.
6. Uses a color LCD screen to display discharge waveforms and magnitude, providing a more user-friendly and intuitive display.
7. Can display single-channel discharge waveforms and trend graphs, as well as dual-channel discharge waveforms.
8. Stores data and waveform screenshots for high-voltage equipment with discharge, facilitating future analysis and comparison.
9. Yellow, green, and red three-level warning values and discharge waveforms are displayed on the same interface for intuitive convenience.
10. Easy to use, compact, lightweight, and portable.
11. No power outage required during detection.
Main Technical Parameters
1. Host: weight not exceeding 0.5kg.
2. Power Supply
(1) Internal battery: lithium battery;
(2) Operating time: not less than 4 hours.
3. Battery and Charger
(1) Stabilized voltage: 220 V AC;
(2) Frequency: 50 Hz;
(3) Charging current: 500mA;
(4) Charging time: not exceeding 8 hours.
4. TEV Sensor
(1) Sensor: capacitive;
(2) Measurement range: 0-60dBmV;
(3) Resolution: 1dB;
(4) Error: ±1dB;
5. Non-contact Ultrasonic Sensor
(1) Measurement range: -7dBμV-68dBμV;
(2) Resolution: 1dBμV;
(3) Error: ±1dBμV;
(4) Sensor center frequency: 40kHz±1kHz;
6. Contact Ultrasonic Sensor
(1) Measurement range: 0-60dBmV;
(2) Measurement frequency band: 20kHz-200kHz
(3) Resolution: 1dB;
(4) Error: ±1dB;
7. Broadband Current Transformer
(1) Sensitivity: 10pC
(2) Measurement frequency band: 20kHz-30MHz
(3) Range: 10pC-100nC
8. UHF Sensor
(1) Sensitivity: -65dBmV;
(2) Measurement frequency band: 300MHz-3GHz
(3) Measurement range: -65dBmV-10dBmV;
(4) Resolution: 1 dBmV.

Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.