Three-Phase Power Lightning Counter
Darui Electric recommends:
III. Instructions for the Three-Phase Power Lightning Counter:
1. Please charge before use. To ensure charging efficiency and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. A red light on the charger indicates charging; a green light indicates charging is complete.
2. According to the installation height of the counter, appropriately extend the telescopic discharge rod.
3. For the dedicated grounding wire, insert one end's plug into the jack at the rear of the calibrator, and connect the other end's clip to the ground.
4. Press the red button to apply high voltage for about 1 second. The indicator light will illuminate (flicker slightly),
then you can gently tap the connection end between the counter and the arrester for testing.
5. After each tap, the tip of the discharge rod should be removed from the counter. If repeated testing is needed, do not release the button. Wait 1-2 seconds until the indicator light flickers again, then tap to test again.
6. Continuous testing may cause the calibrator to heat up. Please allow appropriate intervals to reduce malfunctions and extend battery life.
7. The calibrator output has three levels: high, medium, and low, which can be adjusted via the toggle switch on the head to suit testing different types or brands of counters.
8. If the indicator light does not flicker after pressing the button for more than 3 seconds, the battery needs charging.
9. Do not disassemble the calibrator arbitrarily. If the battery capacity significantly drops or charging efficiency is too low, it needs replacement. Please purchase a dedicated battery pack from our company.

Note: The above information and technical parameters are compiled and published by Yangzhou Darui Electric Co., Ltd.