DCL-2G Lightning Protection Component Tester
With a charging function for offline use, it overcomes the disadvantage of traditional products that require plug-in power, which is inconvenient for on-site operation. The voltage output of 2000V expands its application range. It features high-voltage short-circuit protection, automatic discharge function, making the instrument reliable, safe, and durable. At the same time, it adopts a luxurious large color screen display, data storage, data review, pass/fail judgment, automatic shutdown, USB data upload, and other functions. The whole instrument is aesthetically pleasing and high-end, with a wide range, high resolution, convenient operation, easy portability, accuracy, reliability, stable performance, and strong anti-interference capability.
Product Aliases:
Lightning protection component tester, SPD field tester, lightning protection comprehensive tester used for surge arresters, lightning protectors, surge protective devices, varistors, metal-ceramic gas discharge tubes, vacuum lightning arresters, and other performance testing specialized instruments.
Technical Parameters:
|
Function |
Varistor (MOV) starting voltage and leakage current test, gas discharge tube (GDT) discharge voltage test, insulation resistance test |
|
Reference Conditions |
23℃±5℃, below 75%rh |
|
Measurement Voltage (V) |
0~2000V Accuracy ±2%rdg±3dgt |
|
Measurement Leakage Current (uA) |
0.1uA~199.9uA Accuracy ±3%rdg±5dgt |
|
DC Voltage Resolution |
1V |
|
Leakage Current Resolution |
0.1uA |
|
Insulation Resistance |
0~1000MΩ |
|
Test Stabilization Time |
≤3s |
|
Discharge Tube Voltage Rise Rate |
(100±8) V/s |
|
Power Supply |
7.2V large capacity rechargeable battery |
|
Backlight |
Yes, suitable for use in dark places |
|
USB Data Transfer |
Yes |
|
Display Mode |
5-inch color TFT LCD |
|
LCD Display Size |
108mm×65mm |
|
Instrument Dimensions |
240mm (length)×188mm (width)×85mm (height) |
|
Test Leads |
Red test lead 1 meter, black test lead 1 meter |
|
Data Storage |
500 groups |
|
Data Review |
Data review function: "MR" symbol display |
|
Overflow Display |
Overrange overflow function: "OL" symbol display |
|
Judgment Function |
Measurement value exceeds set range |
|
Power Consumption |
Standby: 150mA Max |
|
Measurement: 880mA Max |
|
|
Weight |
1230g (including battery) |
|
Battery Voltage |
Low battery voltage, displays low battery symbol " " |
|
Automatic Shutdown |
Instrument shuts down after 15 minutes of no operation |
|
Insulation Resistance |
≥50MΩ (1000V) |
|
Withstand Voltage |
AC3kV/50Hz 1min |
|
Operating Temperature and Humidity |
-10℃~+50℃<85%RH |
|
Storage Temperature and Humidity |
-15℃~+55℃<90%RH |
|
Applicable Safety Standards |
IEC61010-1, IEC1010-2-31, IEC61557-1,5, IEC60529(IP54), pollution degree 2, CAT Ⅲ 300V |
Product Features:
●DCL-2G Lightning Protection Component Tester is suitable for measuring DC parameters of overvoltage protection components such as zinc oxide surge arresters (varistors), metal-ceramic two-electrode and three-electrode gas discharge tubes, and vacuum lightning arresters. It can also be used as a voltage regulator or constant current power supply for other applications.
●It has high-voltage short-circuit protection, overcurrent protection, high-voltage preset, range adjustment, and other functions. The high-voltage self-discharge time is less than 0.5 seconds.
●It has a self-check function.
●Measurement data is displayed on a three-and-a-half-digit LCD, with high accuracy and good reliability.
●During measurement, the range can be preset, and an audible alarm is given for overrange measurements during the process, suitable for component grouping and inspection discrimination.
●Selecting continuous measurement allows uninterrupted testing of batch samples.
●The panel functions are simple and easy to operate.
●Lightweight and portable.