Three-level contracting (repair, installation, testing) electric power facilities
Series Variable Frequency Resonant Test System: Contracting and testing instruments:
Power frequency AC withstand voltage test device. Ground continuity tester. Transformer DC resistance tester. Transformer turns ratio tester. Transformer winding deformation tester. On-load tap changer tester. Circuit breaker characteristic tester. Zinc oxide arrester resistive current tester. Three-phase relay protection tester. Lightning counter calibration instrument. Insulation resistance tester. Megohmmeter. Dual-clamp phase digital volt-ampere meter.
Configuration table of main test equipment for three-level repair, installation, and testing qualifications
|
No. |
Equipment Name |
Specification/Model |
Quantity |
Application Range / Purpose |
||||
|
I. High Voltage Generation Equipment |
||||||||
|
1 |
DC High Voltage Generator |
ZGF-200KV/3mA |
1 set |
DC: 200kV/3mA for testing transformers, arresters, and DC withstand voltage test |
||||
|
|
DC High Voltage Generator |
DC: 120kV/2mA |
1 set |
DC: 120kV/2mA for testing transformers, arresters, and DC withstand voltage test |
||||
|
2A |
Power Frequency AC Withstand Voltage Test Complete Set |
TQSB-10KVA/110KV |
1 set |
AC: 10kVA/110kV for transformers, switches, PT/CP/reactors (35kV) |
||||
|
2B |
TQSB -5KVA/50KV |
1 set |
AC: 5kVA/50kV for transformers, cables, arresters, etc. AC withstand voltage (10kV) |
|||||
|
3 |
Variable Frequency Series Resonant Test Complete Set |
GHXZ-500kVA/200kV |
1 set |
500kVA/200kV/2.5A/30-300Hz for cables, transformers, etc. |
||||
|
4 |
Induction Withstand Voltage Test Device |
SBF-15kVA/600V |
1 set |
15kVA/600V 150Hz for induction withstand voltage test on graded insulated electrical equipment |
||||
|
II. Electrical Measuring Instruments |
||||||||
|
1 |
Loop Resistance Tester |
GHL-100A |
2 units |
DC: ≥100A for high-voltage switches, GIS, disconnectors |
||||
|
2 |
Transformer Volt-Ampere Characteristic Tester |
HGQ-600 |
1 unit |
(1100V/5A) for 110kV current transformers (CT/PT) |
||||
|
3 |
Capacitance and Inductance Tester |
GHRG |
1 unit |
Three-phase simultaneous measurement, for capacitors and inductors |
||||
|
4 |
Ground Continuity Tester |
GHJD-10A |
1 unit |
Continuity of the connection between power equipment and ground grid |
||||
|
5 |
Transformer Winding Deformation Tester |
GHBX-III |
1 unit |
Frequency response method |
||||
|
6 |
Circuit Breaker Dynamic Characteristic Tester |
GKC-H |
2 units |
Class 0.2, 12 breaks |
||||
|
7 |
Zinc Oxide Arrester Resistive Current Tester |
YHX-10A |
1 unit |
DC: ≤1A for transformers |
||||
|
8 |
Three-Phase Relay Protection Tester |
GHJB-300 |
1 unit |
Three-phase voltage, two groups each of voltage and current |
||||
|
9 |
Transformer On-Load Tap Changer Tester |
BYKC-2000 |
1 unit |
≥1A to check the complete action sequence of the switching switch and contacts |
||||
|
10 |
High Voltage Dielectric Loss Tester |
GHJS |
2 units |
For dielectric loss test on transformers, instrument transformers, bushings, etc. |
||||
|
11 |
Lightning Counter Operation Tester / Rod Type |
FZ-Z |
1 piece |
To check whether the arrester discharge counter operates normally |
||||
|
12 |
Insulation Resistance Tester |
GH2672 |
2 units |
DC: 0-5000V, 200G(MΩ) short circuit current ≥3mA |
||||
|
13 |
Ground Grid Earth Resistance Tester |
GHDW-5A |
1 unit |
Heterodyne method, to check the earth resistance of the ground grid |
||||
|
14 |
Transformer DC Resistance Tester |
ZGY-10A |
2 units |
For DC resistance test on transformers |
||||
|
15 |
Transformer Turns Ratio Tester |
GHBZC |
1 unit |
Class 0.5, digital |
||||
|
III. Oil and Gas Test Instruments |
||||||||
|
1 |
SF6 Leak Detector |
XP-1A |
1 unit |
SF6 gas leak detection and measurement |
||||
|
5 |
Moisture Meter |
GHWS |
1 unit |
Measurement of trace moisture in SF6 gas |
||||
|
IV. Common Instruments and Meters |
||||||||
|
1 |
Megohmmeter |
BY2671 |
1 piece |
DC: 2500V for transformers, cables, lines, etc. |
||||
|
2 |
Megohmmeter |
BY2670 |
1 piece |
DC: 500V for transformers, cables, lines, etc. |
||||
|
3 |
Digital Dual-Clamp Phase Volt-Ampere Meter |
SMG2000 |
1 piece |
Measurement current less than 50mA, measures voltage, current, and phase |
||||