160V Transformer Turns Ratio Tester - Four-Level Testing Qualification Equipment Function



The fully automatic transformer turns ratio and group tester is mainly used in the production process of semi-finished and finished power transformers, before new transformers are put into operation, and during the operation of transformers in the power system. According to the preventive test regulations of the Ministry of Electric Power, it is required to regularly test the turns ratio or voltage ratio of operating transformers. The traditional ratio bridge is cumbersome to operate, the readings are not intuitive, and necessary conversions are required. The test result only provides data for one phase ratio. The fully automatic transformer turns ratio and group tester overcomes the shortcomings of traditional ratio bridge testing. The screen completes the three-phase ratio test in one go, with fast test speed and high accuracy. It greatly saves on-site testing time and brings high efficiency to customers' tests.



160V Transformer Turns Ratio Tester - Four-Level Testing Qualification Equipment Precautions:

1. Before using this instrument, be sure to read this operation manual carefully.

2. The operator of the instrument should have general knowledge of electrical equipment or instruments.

3. This instrument can be used indoors and outdoors, but should avoid rain, corrosive gases, excessive dust, high temperature, and direct sunlight.

4. The instrument should avoid severe vibration.

5. Maintenance, care, and adjustment of the instrument should be carried out by professionals.

6. The yellow, green, and red test clips correspond to phases A, B, and C of the transformer, respectively. Do not connect them incorrectly.

7. Do not reverse the high and low voltage cables.

8. When testing a single-phase transformer, only use the yellow and green clips. Do not use them incorrectly, and leave unused test clips suspended.



Product Features:

1. The fully automatic transformer turns ratio and group tester has a wide test range, up to 10000.

2. Fast test speed, completing three-phase test in 7 seconds.

3. Test for Z-connected transformers.

4. Has blind test function for turns ratio and group test. (When blind testing, the high-voltage side connection method must be known.)

5. Non-volatile clock and date display, data storage function.

6. Protection function against reverse connection of high and low voltage.

7. Protection function against transformer short circuit and inter-turn short circuit.

8. Thermal printer output function, fast and silent.

9. Small size, light weight.

Technical Parameters:

1. Range: 0.9~10000

2. Accuracy: 0.1%  + 1 digit (below 500)

       0.2% + 2 digits (500~2000)

       0.3% + 1 digit (2000~4000)

       0.5% + 1 digit (above 4000)

3. Resolution: minimum 0.0001

4. Output voltage: 160V, 10V automatic gear shifting

5. Working power supply: AC220V  50HZ

6. Operating temperature: –20℃~ 40℃

7. Relative humidity: ≤85%, no condensation