Loop Resistance Tester with Printing


Precautions

Fault Phenomenon Cause Analysis Troubleshooting Method Remarks
No display upon power-on 1) Power not connected Connect the power supply When replacing the fuse, use the same type of fuse; do not substitute with other types.
2) The instrument's 5A fuse is not installed properly or is open Reinstall the fuse or replace it    
Output current cannot reach 200A 1) Test line is too long, i.e., wire cross-sectional area is too small Replace with wires of larger cross-sectional area  
No current output 1) The device under test is open circuit Check the device
Troubleshoot the fault
 
Open circuit fault in the test loop Check the test loop and eliminate the open circuit fault    





1. Before turning on the power switch, ensure the test button is released (not in test state) and the current adjustment knob is turned counterclockwise to the "zero" position.



2. The instrument should be placed in a dry, ventilated room without corrosive gases.

3. After testing, wait until the power is completely discharged before removing test leads and other devices.

Transportation and Storage


1. Transportation

When the equipment needs to be transported, it is recommended to use the company's instrument packaging wooden case and shock-absorbing materials to avoid unnecessary damage during transit and prevent unnecessary losses.
When the equipment is transported without a wooden case, stacking is not allowed. When using the company's instrument packaging case, the maximum stacking layers allowed is two.
During transportation, the instrument panel should face upward.
2. Storage

The equipment should be stored in a dry, dust-free, ventilated room without corrosive gases. Without wooden case packaging, stacking is not allowed.
When storing the equipment, the panel should face upward. Place moisture-proof materials at the bottom of the equipment to prevent moisture.