This system is suitable for induced withstand voltage and partial discharge testing of distribution and power transformers. The system background noise is not greater than 5pc, and the partial discharge signal is clear, making it an ideal device for transformer induced withstand voltage and partial discharge testing.
This control console serves as the central control unit, which can control operations to produce a 40-800V 125Hz, 150Hz, 200Hz adjustable power supply from the generator set.
Frequency multiplier withstand voltage machine, frequency multiplier withstand voltage test device, triple frequency withstand voltage test device.
◆This control cabinet can only start the medium frequency power supply function when the voltage regulator starts at zero position, ensuring that the medium frequency power supply outputs from a low potential.
◆After the motor starts via Y-△, the medium frequency indicator light will illuminate before the medium frequency power supply can be started, ensuring the motor starts at full voltage.
◆The motor has thermal relay protection; when the motor overheats, the main circuit is cut off, and the voltage regulator automatically returns to zero position.
◆When the excitation power supply current and the medium frequency output power supply are overloaded, the overcurrent relay operates, cutting off the main circuit, and the voltage regulator automatically returns to zero position.
Device Parameters:
Motor Technical Parameters:
◆Rated Capacity: 30KW
◆Input Voltage: Three-phase four-wire AC380V ±10%
◆Input Current: 75A
◆Input Frequency: 50Hz ±2Hz
◆Power Factor: cosφ0.8
Generator Technical Parameters:
◆Rated Capacity: 40KVA
◆Power Factor: cosφ0.5
◆Output Capacity: 20KW
◆Output Voltage: 40~800V AC
◆Output Current: 25A
◆Output Frequency: 150Hz ±2Hz
◆Excitation Mode: DC excitation regulation
Working Environment:
◆Ambient Temperature: -15°C –45°C
◆Relative Humidity: ≤85%RH
◆Altitude: ≤2500 meters