With the development of society, people have increasingly higher requirements for the safety and reliability of electricity use. High voltage circuit breakers play a dual role of control and protection in the power system, and their performance directly affects the safe operation of the power system. Mechanical characteristic parameters are one of the important parameters for judging the performance of circuit breakers. The GKC-E high voltage switch mechanical characteristic tester is designed based on the latest "High Voltage AC Circuit Breakers" GB1984-2003, and in accordance with the People's Republic of China electric power industry standard "General Technical Conditions for High Voltage Test Equipment" Part 3, DL/T846.3-2004 high voltage switch comprehensive tester as the design basis, providing convenience for dynamic analysis of various types of circuit breakers, and can accurately measure the mechanical dynamic characteristic parameters of various voltage levels of low oil, multi oil, vacuum, sulfur hexafluoride and other high voltage circuit breakers.

III. Technical Indicators

Environmental group: Belongs to Group III instruments in GB6587.1-1986 "General Outline for Environmental Testing of Electronic Measuring Instruments".

Type: Portable Packaging: Aluminum alloy case

Dimensions and weight::

Main unit: 440×300×150 (mm) 5 (kg)

Accessories: 440×300× 80 (mm) 3 (kg)

Working power supply: AC220V ±10% Frequency: 50Hz ±5%

Ambient temperature: -10°C~40°C Relative humidity: ≤85%

Insulation resistance: ≤2MΩ 

Dielectric strength: The power input line to the casing can withstand a withstand voltage test of 1.5KV for 1 minute.

Time test range: 1~499.9ms Resolution: 0.01ms Accuracy ≤0.1ms

Speed test range: 15m/s Resolution: 0.01m/s Accuracy ±1% reading 2 digits

Stroke test range: unlimited Resolution: 0.01mm Accuracy ±1% reading 2 digits

Product parameters  



1. Input characteristics  



Active part:  



Voltage measurement range: 0~10V.  



Current measurement range: 0~10A.  



Passive part:  



Voltage measurement range: 0~750V wide range.  



Current measurement range: 0~100A, all internal automatic range switching.  



2. Accuracy  



Voltage: ±0.5%.  



Current: ±0.5%.  



Power: ±0.5% (CosΦ>0.2), ±1.0% (0.02



3. Working temperature: -10℃~+40℃  



4. Charging power supply: AC 160V~260V  



5. Insulation:  



(1) Insulation resistance between voltage and current input terminals and the casing ≥100MΩ.  



(2) The working power input terminal to the casing withstands a power frequency of 2kV (effective value) for 1 minute test.  



6. Main unit volume: 32cm×24cm×13cm  



7. Weight: 3k


DC power supply selection range: 25-265V/10A Resolution: 1V: Accuracy ≤±1%