The triple frequency generator is used for testing power transformers, voltage transformers, and other test objects. In addition to performing external power frequency high-voltage tests on the main insulation of fully insulated transformers, it is also necessary to conduct induced high-voltage tests on the longitudinal insulation of transformers and the main insulation of semi-insulated transformers. According to national test standards, the induced test voltage for power transformers and voltage transformers is generally considered to be 2-3 times the maximum working phase voltage. As is well known, when a transformer operates at rated frequency and rated voltage, the iron core is close to saturation. If a test voltage higher than the rated voltage is applied across the winding of the transformer under test using a power frequency power source, the no-load excitation current will increase sharply to an unacceptable level. From the relationship of induced electromotive force, it can be seen that in order to apply a test voltage higher than the rated voltage without saturating the iron core, the method of increasing the power supply frequency can be adopted, and a power source generator with a frequency greater than the power frequency must be used.
Alternative Names Edit
Triple frequency induced withstand voltage device, triple frequency generator, triple frequency induced voltage generator, triple frequency test transformer device, triple frequency induced withstand voltage generator, triple frequency test transformer, triple frequency tester, triple frequency induced withstand voltage tester, triple frequency power source generator.
Purpose Edit
SBF adopts a three-core five-column structure, selecting the working magnetic flux density of the iron core above the saturation magnetic flux density, so that the vector sum of the fundamental electromotive force (positive sequence vector) in the secondary winding connected in an open delta is zero, while the two ends of the open delta output the same-phase 150Hz third harmonic (zero sequence).
Characteristics Edit
Simple operation, reliable performance, and can well meet the needs of induced withstand voltage tests for transformers and instrument transformers.
Working Principle Edit
Adopting power electronics technology, the internal core part uses a variable frequency regulator. Parameter presetting, protection settings, frequency selection, voltage regulation control, etc. Adopting touch operation mode, test frequencies of 50Hz, 100Hz, 150Hz, 200Hz can be preset (optional), and voltage can be adjusted by touch (step size can be adjusted in real time, with options of 1V, 2V, 5V, 10V), enabling the device to output multi-frequency test voltages.
Built-in LC filter circuit ensures that the waveform distortion rate is within the specified range.
Since the traditional three-phase five-column triple frequency generator principle is abandoned, the following advantages are brought:
1. Small size, light weight, easy to carry, and convenient for high-power applications.
2. Not only can it generate triple frequency, but it can also generate test voltage outputs at 1, 2, 3, and 4 times the frequency.
3. Simple operation and wiring, and greatly reduces the requirements for on-site test power supply capacity