Product Application:
It is specially developed under the guidance of the expert working group of reactive power compensation devices to address the problems existing in measuring the capacitance of individual capacitors in parallel capacitor banks at substations. It focuses on solving the following problems:
(1) On-site measurement of individual capacitors requires removing connecting wires, which is not only labor-intensive but also prone to damaging the capacitors;
(2) The low output voltage of capacitance meters leads to a low fault detection rate.
(3) Measuring the inductance of reactors. This instrument features small measurement workload, fast and simple operation, stable performance, accurate measurement, and high fault detection rate.
In addition, its current measurement unit can also be used for measuring electrical equipment such as CVTs and surge arresters, providing multi-functional capabilities in one device.
Technical Parameters:
1. Capacitance range: 0.2μF~2,000μF;
Capacity range: 5~20,000 kvar;
Measurement accuracy: ±1.5%×reading±2 digits;
Resolution: ±1.0%rdg;
2. Inductance range: 1mH~9.99H; Measurement accuracy: ±1.5%±2 digits
3. Output measurement voltage: AC 26V/500VA; 50Hz;
4. Display method: Large-screen LCD with full Chinese output, TPμp-40 panel-type thermal printer
5. Dimensions and weight: 370×370×220 mm / 8 kg
6. Working conditions:
Ambient temperature: 0℃ ~ +40℃, Relative humidity: ≤90%
Power supply: AC 220V±10%; 50Hz;
Measurement range, resolution, and error values
|
Capacitance measurement range: |
Error value: |
|
0.020μF ~ 0.200μF |
±0.5% |
|
0.200μF ~ 2.000μF |
±0.5% |
|
2.000μF ~ 20.00μF |
±0.5% |
|
20.00μF ~ 200.0μF |
±0.5% |
|
200.0μF ~ 2000.μF |
±0.5% |
|
Capacitor reactive power |
0 ~ 20.00Mvar |
Error value |
±1% |
|
Capacitor active power |
0 ~ 20.00kW |
Error value |
±1% |
|
Capacitor dissipation factor |
0 ~ 20.00% |
Error value |
±1% |
|
Capacitor resistance component |
0 ~ 10.00MΩ |
Error value |
±1% |
|
Inductance measurement range |
Error value |
|
0.10mH ~ 0.200H |
±0.5% |
|
2.000H ~ 20.00H |
±0.5% |
|
20.00H ~ 200.0H |
±0.5% |
|
200.0H ~ 2000.H |
±0.5% |
|
Inductor reactive power |
0 ~ 20.00Mvar |
Error value |
±1% |
|
Inductor active power |
0 ~ 20.00kW |
Error value |
±1% |
|
Inductor dissipation factor |
0 ~ 20.00% |
Error value |
±1% |
|
Inductor resistance component |
0 ~ 10.00MΩ |
Error value |
±1% |
Clamp sensor measurement range and error (component)
|
Current measurement range (AC) |
Error value |
|
0.000mA ~ 50.00A |
±0.2%
|
Product Features:
(1) Automatic range conversion;
(2) Stores 2000 test data;
(3) Large-screen LCD (320×240 LCD) display, Chinese menu operation prompts;
(4) Realizes simultaneous display of waveform and measurement data on the same screen, making the test process more intuitive;
(5) Has setting, calibration, and debugging functions.
It features small measurement workload, fast and simple operation, stable performance, accurate measurement, and high fault detection rate; it can also measure the inductance of reactors, discharge resistance measurement function, measure the current and capacitance of coupling capacitors under live conditions, calculate the capacity of the measured capacitance; simultaneously display voltage and current waveforms and phase; automatic range conversion, data storage; large-screen LCD display, Chinese output, and printing capability.
Working Principle:
Due to the use of synchronous sampling technology for standard capacitors and tested capacitors, it is not affected by power supply voltage fluctuations; moreover, the measurement process is fully automatic, avoiding errors caused by manual operation, thus featuring good stability, repeatability, accuracy, and reliability.