Features of Battery Capacity Discharge Tester
◆Suitable for 48V, 110V, 220V, and 380V systems simultaneously.
◆During discharge, monitor the voltage of each individual battery in real time.
◆Can monitor total voltage, total current, and discharged capacity of each individual battery when discharging online equipment of battery banks.
◆Four automatic alarm/stop functions: ①Total voltage termination condition ②Individual voltage termination condition ③Discharge time termination condition ④Discharge capacity termination condition.
◆All Simplified Chinese menu, user-friendly interface, simple operation, clear process.
◆Adopts advanced one-key flywheel operation, eliminating conventional controls such as panel, switches, and control knobs.
◆Equipped with RS232 communication interface and USB interface. Single-unit data can be saved, also can be uploaded to computer or U disk for storage, displayed and printed on other computers.
◆Equipped with special load to meet the needs of larger discharge current.
◆Display collected discharge data in the form of bar charts, reports, and curves on the screen, and print out various effects for convenient analysis.
★Technical Specifications:
◇Input power supply voltage is the battery voltage:
DC220V, range 160~280V
DC110V, range 80~150V
DC48V, range 3.8~60V
Individual battery measurement range: 2V, 6V, 12V
Number of batteries measured: 24 (basic unit, expandable)
Discharge current:
220V/50A, 110V/100A, 48V/150A (basic unit of discharge host)
◇Current accuracy: 1%
◇Voltage accuracy: 0.5%
◇Discharge termination voltage: set according to user requirements
◇Cooling method: forced air cooling
◇Voltage test accuracy: 1%
◇Ambient temperature: 5~40℃
◇Ambient humidity: 5% - 90%
◇Weight: 18kg

Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.