LYYB-3000 Handheld Zinc Oxide Arrester Live Tester Handheld Zinc Oxide Arrester Live Tester
Panel Description:
1---Reference voltage input terminal; 2---Antenna; 3---Measurement ground terminal;
5---Power switch; 6---Charging socket; 8---Leakage current input terminal;
9---Liquid crystal display; 10—Touch keyboard
Main Technical Parameters
Total current measurement range: 0~10mA RMS
Accuracy: ±(reading×5%+5uA)
Resistive current fundamental measurement accuracy (wired, excluding interphase interference): ±(reading×5%+5uA)
Current harmonic measurement accuracy: ±(reading×10%+10uA)
Current channel input resistance: ≤2Ω
Reference voltage input range: 25V~250V RMS
Accuracy: ±(reading×5%+0.5V)
Voltage harmonic measurement accuracy: ±(reading×10%)
Reference voltage channel input resistance: ≥1800kΩ
Battery continuous working time: more than 36 hours
Battery charging time: more than 5 hours
AC charger:
Instrument dimensions: 25cm×5cm×13cm Instrument weight: 0.5kg (excluding cable box)

Note: The above information and technical parameters are compiled and released by Yangzhou Dary Electric Co., Ltd.