GKC-F High Voltage Switch Dynamic Characteristics Tester Uses * Measure the volt-ampere characteristics of linear resistance elements;
* Measure the forward and reverse volt-ampere characteristics of ordinary diodes;
* Measure the forward and reverse volt-ampere characteristics of Zener diodes;
* Measure the volt-ampere characteristics of small bulbs.
Technical Parameters and Features
* DC regulated power supply: two ranges of 2V and 20V available, continuously adjustable, three and a half digit digital display;
* Voltage display: range 0~200V, three and a half digit digital display;
* Current display: four ranges of 200uA, 2mA, 20mA, 200mA available, three and a half digit digital display;
* All use national standard connectors for manual circuit connection, which can cultivate hands-on ability.
GKC-F High Voltage Switch Dynamic Characteristics Tester Other names:
High voltage switch dynamic characteristics tester, switch mechanical characteristics tester, high voltage switch comprehensive tester, circuit breaker dynamic characteristics tester, circuit breaker mechanical characteristics tester, circuit breaker comprehensive tester, high voltage switch time characteristics tester, high voltage switch characteristics tester, switch characteristics tester, circuit breaker tester, switch mechanical characteristics tester,
Main uses: Suitable for mechanical characteristics testing of high voltage circuit breakers of various types (multi-oil, low-oil, SF6, vacuum, etc.) from imported and domestic manufacturers. Also suitable for time testing of electromagnetic action electrical appliances (such as contactors, relays, etc.).
Main features: The instrument has a built-in DC operating power supply, and can flexibly use external operating power supply or external synchronous trigger. Large screen LCD display, can preset typical switch speed definitions; can switch time waveform diagram display of 1 channel close/open command, 12 channels time jumps; S-T graphic display of close/open movement curve, and can dynamically analyze and calculate; V-S curve to visually observe movement speed; I-T curve to observe the action process of electromagnet. Microcomputer printer prints data for retention. The instrument can save 255 test records, and can communicate with computer. Data management software can analyze, correct, and print test reports. The accessory box is equipped with sensors such as 0.1mm, 1mm linear, 1 degree angle photoelectric auxiliary contacts, and complete accessories such as test wires and speed measurement mounting brackets.