● On-site measurement of individual capacitors requires removing connecting wires, which is not only labor-intensive but also prone to damaging the capacitors.
● The low output voltage of the capacitance meter leads to a low fault detection rate.
● Measure the inductance of reactors.
This instrument features minimal measurement workload, quick and simple operation, stable performance, accurate measurement, and a high fault detection rate. Additionally, its current measurement unit can also be used for measuring electrical equipment such as CVTs and arresters, offering multi-functionality in one device.
According to the "Technical Measures for Preventing Accidents in Capacitor Installations," for high-voltage shunt capacitor banks, the capacitance of individual capacitors in the bank should be measured periodically. It is recommended to use a measurement method that does not require disconnecting the connecting wires, to avoid faults such as oil leakage from the bushing due to stress caused by disassembling and assembling the connecting wires.
Functional Features
● Automatic range conversion;
● Stores 7168 test data points;
● Large-screen LCD (320×240 LCD) display with Chinese menu operation prompts;
● Displays waveforms and measurement data on the same screen, making the testing process more intuitive;
● Equipped with setting, calibration, and debugging functions.
Technical Parameters
● Capacitance range: 0.2μF to 2,000μF;
Capacity range: 5 to 20,000 kvar;
Measurement accuracy: 0.2μF to 2μF ±1% reading ±0.02μF;
2μF to 2,000μF ±1% reading ±2 digits;
● Inductance range: 1mH to 9.99H; Measurement accuracy: ±1.5% reading ±2 digits
● Output measurement voltage: AC 26V/500VA; 50Hz;
● Display: Large-screen LCD with full Chinese output, TPμp-40 panel-type thermal printer
● Dimensions / Weight: 370×370×220 mm / 16 kg
● Operating conditions:
a. Ambient temperature: 0℃ to +40℃, relative humidity: ≤90%
b. Power supply: AC 220V±10%; 50Hz;