The lightning protection element tester is an instrument suitable for testing the DC parameters of overvoltage protection components such as zinc oxide arresters (zinc

It has functions such as memory, calculation, hold, self-check, and leakage alarm. It has high-voltage short-circuit protection, overcurrent protection, high-voltage preset, and other functions. The high-voltage self-discharge time is less than 5 seconds. The test results are displayed by two 3 1/2 LCD digital displays, one showing the voltage value and the other showing the current value, with high accuracy and good reliability. It can be used as an adjustable DC high-voltage source (1kV~10kV) with output current ≤1mA.

oxide valve plates and varistors) DC parameters.

Technical Parameters

Withstand voltage: AC 2.3kV 50Hz 1min

Operating temperature and humidity: 0℃~+40℃ <90%RH

Storage temperature and humidity: -10℃~+50℃ <90%RH

Power supply: AC220V±10% 50Hz

Power consumption: <40W

Dimensions: 280mm(L)×280mm(W)×90mm(D)

Weight: ≤4 kg

Main features of the lightning protection element tester:

(1) Suitable for testing DC parameters of overvoltage protection components such as zinc oxide arresters (varistors), metal ceramic two- and three-electrode discharge tubes, vacuum lightning arresters, etc.

(2) It has functions such as high-voltage short-circuit protection, overcurrent protection, high-voltage preset, and range adjustment.

(3) It has a self-check and discrimination function, which can issue an audible prompt for over-range tests during measurement.

(4) It has functions of memory, calculation, hold, control, and continuous testing.

(5) The test results are displayed by a 3 1/2-digit LCD digital display, which can automatically display accurate and reliable required data.

Technical indicators of the lightning protection element tester:

(1) Varistor measurement
Technical Indicator Measurement Range Working Error Test Condition
Initial action voltage U1mA 0~1999V ≤±1%±1d 1mA±5μA
Leakage current I0.75U1mA 0~199.9μA ≤±2μA±1d 0.75U1mA
≤±1%±1d

(2) Discharge tube measurement

Technical Indicator Measurement Range Working Error Test Condition
DC breakdown voltage Vsdc 8~1999V ≤±1%±1d Voltage rise rate
100V/S±10%

(3) Other indicators

Insulation resistance: ≥10MΩ (500V)

Withstand voltage: AC 2kV 50HZ 1min

Operating temperature and humidity: -5℃~+40℃ ≤85%RH

Storage temperature and humidity: -10℃~+50℃ ≤85%RH

Power supply: AC 110V/220V 50Hz/60Hz

DC 12V 0.5A

Power consumption: 10W