1. Capacitance range: 0.2μF~2,000μF;
Capacity range: 5~20,000 kvar;
Measurement accuracy: ±1.5%×reading±2 digits;
Resolution: ±1.0%rdg;
2. Inductance range: 1mH~9.99H; Measurement accuracy: ±1.5%±2 digits
3. Output measurement voltage: AC 26V/500VA; 50Hz;
4. Display mode: large screen LCD with full Chinese output, TPμp-40 panel thermal printer
5. Dimensions and weight: 370×370×220 mm/ 8 kg
6. Working conditions:
Ambient temperature: 0℃ ~+40℃, relative humidity: ≤90%
Power supply: AC 220V±10%; 50Hz;
Measurement range, resolution and error values
| Capacitance measurement gear: | Error value: |
| 0.020μF ~ 0.200μF | ±0.5% |
| 0.200μF ~ 2.000μF | ±0.5% |
| 2.000μF ~ 20.00μF | ±0.5% |
| 20.00μF ~ 200.0μF | ±0.5% |
| 200.0μF ~ 2000.μF | ±0.5% |
| Capacitor reactive power | 0 ~ 20.00Mvar | Error value | ±1% |
| Capacitor active power | 0 ~ 20.00kW | Error value | ±1% |
| Capacitor dissipation factor | 0 ~ 20.00% | Error value | ±1% |
| Capacitor resistance component | 0 ~ 10.00MΩ | Error value | ±1% |
| Inductance measurement gear | Error value |
| 0.10mH ~ 0.200H | ±0.5% |
| 2.000H ~ 20.00H | ±0.5% |
| 20.00H ~ 200.0H | ±0.5% |
| 200.0H ~ 2000.H | ±0.5% |
| Inductor reactive power | 0 ~ 20.00Mvar | Error value | ±1% |
| Inductor active power | 0 ~ 20.00kW | Error value | ±1% |
| Inductor dissipation factor | 0 ~ 20.00% | Error value | ±1% |
| Inductor resistance component | 0 ~ 10.00MΩ | Error value | ±1% |