The instrument can measure high-voltage electrical equipment that is ungrounded or directly grounded using the positive and reverse wiring methods. At the same time, it can measure the tgδ of capacitive voltage transformers and the capacitance of main capacitors C1 and C2.
The instrument is equipped with a high-voltage step-up transformer and has safety protection measures such as zero-crossing closing and lightning protection. During the test, high voltages of different levels from 0.5KV to 10kV are output, making operation simple and safe.
Tester Characteristics
◆ Simple operation, Chinese display, printing
◆ Convenient to use, no conversion needed
◆ The variable-frequency dielectric loss tester has its own high voltage, strong anti-interference ability, short test time, and other advantages
Tester Features
Tester Parameters
| 1. | Due to the use of frequency conversion technology, accurate measurement can be ensured under strong electric field interference. |
| 2. | The instrument adopts Chinese menu operation, and the microcomputer automatically completes the entire measurement process. |
| 3、 | This instrument is also suitable for measuring the tgδ and capacitance of high-voltage electrical equipment in workshops, laboratories, and scientific research institutions; it also has the advantages of convenience, simplicity, and accuracy for loss testing of insulating oil. |
| 4、 | The instrument can measure high-voltage electrical equipment that is ungrounded or directly grounded using the positive and reverse wiring methods. At the same time, it can measure the tgδ of capacitive voltage transformers and the capacitance of main capacitors C1 and C2. |
| 5、 | The instrument is equipped with a high-voltage step-up transformer and has safety protection measures such as zero-crossing closing and lightning protection. During the test, high voltages of different levels from 0.5KV to 10kV are output, making operation simple and safe. |
1. High voltage output: 0.5 to 10kV, each step increases by 500V, with a total of 20 steps
High voltage output cable can be dragged on the ground for use
Three frequencies: 45Hz, 50Hz, 55Hz
2. Capacity: 1500VA
3. Accuracy: tgδ: ±(reading*1.0%+0.08%)
Cx: ±(reading*1.5%+5PF)
4. Resolution: tgδ: 0.01% Cx: 1pF
5. Measurement range: 0.1% < tgδ < 50%
3PF< Cx < 60000PF
At 10KV, Cx ≤30000PF
At 5KV, Cx ≤60000PF
6. Power supply: AC 220V ±10% 50 ±1Hz
7. Harmonic adaptation: ≤3%
8. Operating conditions: -15℃-50℃, relative humidity <80%
9. Dimensions: 460 (L)×335 (W)×340 (H)
10. Weight: 30 kg