TLHG-801 Three-Phase Zinc Oxide Arrester Tester is simple to operate and convenient to use. The entire measurement process is controlled by a microcontroller. It can measure the total current, resistive current and its harmonics, power frequency reference voltage and its harmonics, active power, and phase difference of zinc oxide arresters. The large screen can display the real waveforms of voltage and current. The instrument uses digital waveform analysis technology, adopts harmonic analysis and digital filtering and other software anti-interference methods to make the measurement results accurate and stable. It can accurately analyze the content of the fundamental wave and the 3rd to 7th harmonics, and can overcome the influence of inter-phase interference, correctly measuring the resistive current of the side-phase arrester. The TLHG-801 Three-Phase Zinc Oxide Arrester Tester is equipped with a high-speed panel printer and rechargeable battery, making it very convenient for test personnel to use on site. The TLHG-801 Three-Phase Zinc Oxide Arrester Tester uses a unique high-speed magnetic isolation digital sensor to directly collect input voltage and current signals, ensuring the reliability and safety of data. [1]
Product Features
1. This machine adopts a large-screen liquid crystal display, full Chinese menu operation, and is easy to use.
2. High-precision sampling and processing circuits, advanced Fourier harmonic analysis technology, ensuring more reliable data.
3. The instrument uses a unique high-speed magnetic isolation digital sensor to directly collect input voltage and current signals, ensuring the reliability and safety of data.
4. This instrument can use the method of electric field induction instead of PT secondary wiring.
5. No voltage mode, no need to take PT secondary voltage signal, using software calculation method to find the voltage reference.
6. This instrument can measure three phases simultaneously with automatic compensation, making it especially convenient to use.
7. It has functions such as resistive current fundamental peak output and side-phase correction.
8. The instrument is equipped with a rechargeable battery, calendar clock, and micro printer, and can store 120 sets of measurement data.
Product Parameters
1. Total current measurement range: 0-10mA RMS, 50Hz/60Hz Accuracy: ±(reading×5%+5µA)
2. Resistive current fundamental measurement accuracy (secondary method without inter-phase interference): ±(reading×5%+5µA)
3. Current harmonic accuracy: ±(reading×10%+10µA)
4. Reference voltage input range: 25V-250V RMS, total harmonic content <30% 50Hz/60Hz
5. Reference voltage measurement accuracy: ±(reading×5%+0.5V)
6. Voltage harmonic measurement accuracy: ±(reading×10%)
7. Fundamental current and voltage angle Φ: 0°-360°
8. Electric field strength input range: 30KV/m-300KV/m, total harmonic content <30%
9. Electric field strength measurement accuracy: ±(reading×10%)
10. Electric field harmonic measurement accuracy: ±(reading×10%)
11. Battery working time: 6 hours for the main unit
12. Charging power supply: 220V±10% 50Hz/60Hz
Charging time: >5 hours
13. Working environment: Temperature: -10-50℃ Humidity: <90%