1. The cable fault tester adopts an industrial embedded computer platform system, designed for industrial-grade environments to achieve extremely high stability. Powered by a lithium battery, it is convenient for on-site testing.
2. It features a 12.1-inch large touch screen system with fully integrated software on a computer operating platform, completely bidding farewell to the era of single-chip microcomputers in cable testers, and is equipped with cable fault testing management software.
3. It uses a USB communication interface for stable signal acquisition. If paired with a laptop, it can achieve dual control and dual display. The host can automatically select sampling frequencies from as low as 6.25MHz to as high as 100MHz, meeting the testing requirements for cables of different lengths and reducing coarse measurement errors.
4. The software enables automatic fault search and automatic distance display. Dual cursors can be moved with precision up to 0.1 meters, and waveforms can be arbitrarily compressed or expanded. Two waveforms closer to the standard can be randomly displayed on the same screen for accurate comparison and analysis, improving testing accuracy and reducing errors.
5. It can store multiple types of field waveforms and on-site physical wiring diagrams in memory, which can be used with a single click. The cable data management software can perform comprehensive cable file management, providing reference and assistance for cable maintenance and precise location.
6. The intelligent combined sampler replaces cumbersome on-site wiring, making waveforms intuitive and easy to analyze. It is isolated from high voltage, ensuring absolute safety for the host and operators.
Technical Specifications
1. Cable Fault Testing System
(1) Capable of testing various types of faults in power cables, as well as open and short circuit faults in communication and local telephone cables.
(2) Can measure the propagation speed of electrical waves in any cable of known length.
(3) Testing distance: not less than 16 kilometers
(4) System error: less than 1 meter
(5) Sampling frequency: 25MHz
(6) Testing blind zone: less than 10 meters
(7) Power supply: AC 220V±10%
2. Cable Path Signal Generator
(1) Signal frequency: 15KHz
(2) Oscillation mode: intermittent
(3) Output power: 30W
(4) Power supply: 220V±10%
3. Cable Fault Locator
Test sensitivity: With a signal source of 50Ω internal resistance outputting a 300Hz signal, the locator can maintain an output of 2V and a signal-to-noise ratio better than 20:1 when the input signal is not greater than 10μV.
(1) Input impedance: not less than 1.2KΩ
(2) Uses 2×2000Ω headphones
(3) Input operating voltage: DC9V±10%
(4) Operating ambient temperature: -20℃~40℃