Model Configuration Table
(Can be customized according to customer requirements
Cable AC Withstand Voltage Test Series
| Model | Satisfiable Test Items | Equipment Reactor Configuration | Remarks |
| DFVF3000-44/22 | 10kV (300mm) cable 1KM | 22kV x 1 unit | Portable |
| DFVF3000-132/66 | 1. 10kV (300mm) cable 3KM |
2. 35kV (300mm) cable 1KM
| 22kV x 3 units | Portable |
| DFVF3000-264/52 | 1. 10kV (300mm) cable 5KM |
2. 35kV (300mm) cable 2KM
3. 35kV transformers, switches,
4. 10kV motors, transformers
5. Generators up to 600MW and below, etc.
| 22kV x 6 units | Portable | ||
| DFVF3000-1560/66 | 110kV (300mm) cable 3KM | 130kV x 2 units | Non-portable |
Generator Power Frequency Withstand Voltage Test Series
| Model | Satisfiable Test Items | Equipment Reactor Configuration | Remarks |
| DFVF3000-44/22 | 1. Generators up to 100MW and below, phase capacitance 0.1-0.3uF |
2. 10kV (300mm) cable 1KM
| 22kV x 1 unit | Portable |
| DFVF3000-100/36 | 1. Generators up to 600MW and below, phase capacitance 0.1-0.25uF |
2. 10kV (300mm) cable 1.5KM
| 18kV x 2 units | Portable |
| DFVF3000-176/44 | 1. Generators up to 600MW and below, phase capacitance 0.1-0.3uF |
2. 10kV (300mm) cable 3KM 3. Can also cover generator busbars, main transformers, etc.
| 22kV x 4 units | Portable |
GIS and SF6 Switchgear AC Withstand Voltage Test Series
| Model | Satisfiable Test Items | Reactor Configuration | Remarks |
| DFVF3000-250/200 | 1. AC withstand voltage test for 110kV GIS |
2. 35kV (300mm) cable 1KM
3. 10kV (300mm) cable 3KM
4. Power frequency withstand voltage for transformers below 220kV 5. AC withstand voltage for 110kV instrument transformers
| 40kV x 5 units | Portable | ||
| DFVF3000-100/200 | 1. AC withstand voltage test for 110kV GIS 2. AC withstand voltage for 110kV instrument transformers | 50kV x 4 units | Portable |
Power Frequency AC Withstand Voltage Test Series for Transformers, Motors, and Other Equipment
| Model | Satisfiable Test Items | Reactor Configuration | Remarks |
| DFVF3000-105/84 | 1. Power frequency withstand voltage test for 110kV transformers |
2. Power frequency withstand voltage test for 10kV motors 3. AC withstand voltage test for 35kV switches
4. 10kV (300mm) cable 1KM
| 28kV x 3 units | Portable |
| DFVF3000-100/80 | 1. Power frequency withstand voltage test for 110kV transformers |
2. Power frequency withstand voltage test for 10kV motors 3. AC withstand voltage test for 35kV switches
4. 10kV (300mm) cable 1KM
| 40kV x 2 units | Portable |