Power Frequency AC Withstand Voltage Test Complete Set



Product Introduction:



The power frequency withstand voltage test device for substation electrical equipment is designed and manufactured mainly for AC withstand voltage tests of primary electrical equipment in substations up to 220KV. It can meet the requirements for capacitive equipment such as transformers, GIS systems, SF6 switches, cables, and bushings according to regulations. It can satisfy both high-voltage, low-current equipment test conditions and low-voltage, high-current equipment test conditions, with a wide range of applications. It is an ideal withstand voltage device for prefecture, city, and county-level high-voltage testing departments and power installation, repair, and testing engineering units.

Power Frequency AC Withstand Voltage Test Complete Set



It mainly consists of a variable frequency control power supply, excitation transformer, reactor, and capacitive voltage divider. Among them, the variable frequency control power supply adopts an imported special-purpose SPWM digital waveform generation chip with a frequency resolution of 16 bits, and the frequency fineness can reach 0.1Hz in the range of 20-300Hz. At the same time, it adopts orthogonal non-synchronous fixed carrier modulation to ensure good output waveform throughout the entire frequency range; the power part adopts advanced IPM modules to ensure instrument stability and safety.



Compared with similar domestic products, this series of devices has multiple key advantages:

1. The reactors of the same voltage level and capacity are smaller in size and lighter in weight; the temperature rise is small under rated load; they adopt dry-type epoxy casting, with high mechanical strength, good electrical insulation performance, beautiful appearance, and reliability.

2. The variable frequency control source has a large capacity margin; strong protection functions; good output waveform; good stability; multiple working modes, convenient operation; uses 220V or 380V single-phase power supply, convenient for on-site power access.

3. Flexible configuration. Different types of reactors can be optionally configured to meet different test requirements, achieving one machine with multiple uses and high cost performance.



Power Frequency AC Withstand Voltage Test Complete Set Technical Parameters:



◆ Rated output voltage: 0~500KV (AC RMS) and below

◆ Output frequency: 20~300Hz

◆ Resonant voltage waveform: pure sine wave, waveform distortion rate <1.0%

◆ Maximum test capacity: 1000KVA and below

◆ Duty cycle: under full power output, continuous working time of 15min per session

◆ Quality factor: 30~90

◆ Frequency adjustment sensitivity: 0.1Hz, instability <0.05%

◆ Working power supply: 380/220V±15%/50Hz±5%

◆ YG series product configuration and applicable scope