Application and review of the license for installation (repair, testing) of electric power facilities (third-level testing complete device set),

        These conditions are formulated in accordance with the "Measures for the Administration of Licenses for Installation (Repair, Testing) of Electric Power Facilities" (Order No. 28 of the State Electricity Regulatory Commission) and relevant standards of the electric power industry, combined with the actual management of installation (repair, testing) electric power facility licenses and the electric power construction market.

        Article 2 These conditions apply to the application, change, renewal and other licensing matters of installation (repair, testing) electric power facility licenses nationwide. During the construction and operation process, installation (repair, testing) electric power facility enterprises shall, in accordance with national standards, electric power safety production and other regulatory requirements, be equipped with machinery and equipment suitable for the construction and operation activities according to the actual needs of the project.

        Article 3 The conditions for construction machinery and equipment required for installation (repair, testing) electric power facility licenses at all levels include transportation tools, tower assembly and wire laying equipment, insulating oil and gas construction equipment, crimping, welding and cutting equipment, and measurement, testing and power equipment. (See Appendix 1 for details: Third-level testing complete device set)

        Article 4 The conditions for construction machinery and equipment required for repair (installation, testing) electric power facility licenses at all levels include transportation tools, line maintenance construction equipment, insulating oil and gas construction equipment, crimping, welding and cutting equipment, and measurement, testing and power equipment. (See Appendix 2 for details)

        Article 5 The conditions for construction machinery and equipment required for testing (installation, repair) electric power facility licenses at all levels include high-voltage generation equipment, electrical measuring instruments, insulating oil and gas testing instruments, and common instruments and meters.



    Hubei Yitiancheng Electric Power Equipment Co., Ltd. specializes in the R&D and production of testing qualification equipment. The 2017 national general version of the third-level testing equipment list is as follows:



 



No. Equipment Name Quantity Model Main Technical Parameters
1 DC High Voltage Generator 1 set YTCZG-200kV/3mA Output voltage: 200kV     Output current: 3A
Voltage measurement accuracy: digital display ±(1.0% reading ±0.2kV)
Current measurement accuracy: digital display ±(1.0% reading ±2)
0.75UDC1mA function button, convenient for zinc oxide arrester test
1 set YTCZG-120kV/2mA Output voltage: 120kV     Output current: 2A
Voltage measurement accuracy: digital display ±(1.0% reading ±0.2kV)
Current measurement accuracy: digital display ±(1.0% reading ±2)
0.75UDC1mA function button, convenient for zinc oxide arrester test
2 Power Frequency Withstand Voltage Test Device 1 set YD-J-10kVA/100kV AC, capacity: 10kVA, output voltage: 100kV
1 set YD-J-5kVA/50kV AC, capacity: 5kVA, output voltage: 50kV
3 Variable Frequency Series Resonance Test Complete Device Set 1 set YTC850-500kVA/200kV YTC850-500kVA/200kV variable frequency series resonance test complete device set can complete the following tests:
1. AC withstand voltage test of 110kV/63000kVA main transformer
2. AC withstand voltage test of 110kV/300mm2 cable 0.8km
3. AC withstand voltage test of 110kV high-voltage switchgear and GIS
The configuration of YTC850-500kVA/200kV variable frequency series resonance test complete device set is as follows:
1 Excitation transformer JLB-18kVA/2.5/5/10kV/0.4kV 1 unit
2 Variable frequency power supply YTC850-18kW/220/380V 1 unit
3 High-voltage reactor DK-83.3kVA/45kV 6 units
4 Capacitive voltage divider FRC-200kV/750pF 1 set
Induction Withstand Voltage Test Device 1 set YTC1102-5kVA 1. Input voltage: three-phase 380V   50Hz    sine wave
2. Output voltage: 0-500V     150Hz   
waveform distortion ≤5%
3. Output capacity: 5kVA
4. No-load operation time: ≤5 minutes      
5. Load operation time: 40~60S
4 High Voltage Dielectric Loss Tester 2 units YTC309 Capacitance range:
Internal high voltage: 3pF~60000pF/10kV    60pF~1μF/0.5kV
External high voltage: 3pF~1.5μF/10kV   60pF~30μF/0.5kV
Resolution: up to 0.001pF, 4 significant digits
Test current range: 10μA~
CVT self-excitation method low voltage output: output voltage 3~50V, output current 3~30A
Loop Resistance Tester 2 units YTC5501-100 1. Measurement range: 1~1999μΩ
2. Resolution: 1μΩ
3. Test current: DC 100A
4. Measurement accuracy: 0.5%
5. Display: current: three and a half digit LCD
            resistance: three and a half digit LCD
6. Working power supply: AC220V±10% 50Hz
7. Working environment: temperature -10℃~40℃   humidity: ≤80 %RH
5 Transformer Volt-Ampere Characteristic Tester 1 unit YTC8750B 1. Working power supply: 220Vac±10%/50Hz
2. Voltage output: 0~1000Vac (1 peak)
3. Ratio test current output: 0~600A
4. Volt-ampere test current output: 0~20A
5. Ratio detection: range 10000/1, accuracy ±0.5%
6. Working temperature: -10℃~40℃
7. Ambient humidity: ≤90%
8. Altitude: ≤1000m
9. Dimensions: 400mm×300mm×260mm
10. Weight: ≤18kg
Ground Resistance Tester 1 unit YTC2571 1. Operating conditions
      Ambient temperature: 0℃~+45℃
      Relative humidity: ≤85%RH
2. Measurement range and constant current value (effective value)
      Resistance: 0~2Ω(10mA), 2~20Ω(10mA), 20~200Ω(1mA)
      Voltage: AC 0~20V
3. Measurement accuracy and resolution
      Accuracy: 0~0.2Ω≤±3%±1d
           0.2Ω~200Ω≤±1.5%±1d
           1~20V≤±3%±1d
   Resolution: 0.001Ω, 0.01Ω, 0.1Ω, 0.01V
4. Measurement error caused by auxiliary ground resistance and ground voltage
      Allowable auxiliary ground resistance RC (between C1 and C2) <1.8KΩ; RP (between P1 and P2) <40KΩ error ≤±5%
      Allowable ground voltage ≤5V (power frequency effective value) error ≤±5%
5. Power supply and power consumption
      Maximum power loss ≤2W
      DC: 8×1.5V (AA, R6) battery AC: 220V/50Hz
      Dimensions: 220mm×200mm×105mm
      Weight: ≤1.4kg
6 Capacitance and Inductance Tester 1 unit YTC720 1. Capacitance range: 0.2μF~2,000μF;
   Capacity range: 5~20,000 kvar;
   Measurement accuracy: 0.2μF~2μF    ±1% reading ±0.02μF;
            2μF~2,000μF  ±1% reading ±2 digits;
2. Inductance range: 1mH~9.99H; measurement accuracy: ±1.5% reading ±2 digits
3. Output measurement voltage: AC 26V/500VA; 50Hz;
4. Display: large screen LCD full Chinese output, TPμp-40 panel thermal printer
5. Dimensions / weight: 370×370×220 mm / 16 kg
6. Working conditions
   a. Ambient temperature: 0℃ ~ +40℃, relative humidity: ≤90%
   b. Power supply: AC 220V±10%; 50Hz;
Ground Continuity Tester 1 unit YTC2885-10A Measurement current: 10A, 1A
Measurement range: 1A  10mΩ~20Ω
            1μΩ~4Ω
          10A  1μΩ~2Ω
Accuracy: ±0.2% (full scale) ±2 digits
7 Transformer DC Resistance Tester 2 units YTC316-10 Measurement range:
0.01A: 1μΩ~2kΩ      
 1A: 1μΩ~20Ω
: 1μΩ~4Ω         
10A: 1μΩ~2Ω
Measurement error: ±0.2%
Transformer Turns Ratio Tester 1 unit YTC3317 1. Turns ratio measurement range: 1—10000
2. Group: 1—12 points
3. Accuracy: 1-1000 0.2 class
         1000-10000 0.5 class
4. Power supply: AC220V ±10%, 50HZ
5. Operating ambient temperature: -5℃ ─ 40℃
6. Operating ambient humidity: <85%
8 Transformer Winding Deformation Tester 1 unit YTC3223 Through testing, faults such as winding distortion, bulging, displacement, tilting, inter-turn short circuit deformation and phase-to-phase contact short circuit can be accurately diagnosed
The instrument has dual measurement systems: linear sweep measurement and segmented sweep measurement
Amplitude measurement range: (-100dB)–(+20dB)
Amplitude measurement accuracy: 0.1dB  Sweep frequency accuracy: less than 0.01%
Signal input impedance: 1MΩ   Signal output impedance: 50Ω
Same-phase test repeatability: 99.5%
On-load Tap Changer Tester 1 unit YTC3993 Voltage output: >20V
Working power supply: AC220V±10%, 50Hz
Current output: ≥1A
Power: 180W
Resistance measurement range: 0.3~40Ω
Resistance measurement accuracy: 0.1Ω~1Ω±0.1Ω,
          1Ω~40Ω±5%±0.1Ω (excluding 1Ω)
Time measurement range: 1ms~256ms
Time measurement accuracy: 1ms~100ms±0.1ms
    
WeChat QR Code
💬
💬 Online Consultation

Hello! How can I help you?

Leave a Message
Yangzhou DARUI Electric Co., Ltd.
Main Products: Dielectric Loss Tester, Transformer Ratio Tester, Loop Resistance Tester, HV Wireless Phase Detector, Insulation Resistance Tester, Partial Discharge Tester, Cable Fault Tester, DC Resistance Tester, etc.
☎ Tel: 18952707000 (Manager Guan)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
captcha
By submitting you agree to our Terms of Service and Privacy Policy