The GS213 Transformer Capacity Characteristic Tester can accurately measure the capacity of various distribution transformers with passive measurement. It can also measure no-load current, no-load loss, short-circuit voltage, short-circuit loss, and zero-sequence impedance of various types of transformers. It can automatically perform waveform distortion correction, temperature correction, voltage correction (no-load test under non-rated voltage), and current correction (short-circuit test under non-rated current). The operator only needs to input the correction index based on the transformer type, and the instrument will automatically calculate the corrected results. It allows external voltage and current transformers to expand the measurement range, enabling measurement of test objects with any parameters.

Introduction

The Transformer Capacity Characteristic Tester can accurately measure the capacity of various distribution transformers with passive measurement. It can also measure no-load current, no-load loss, short-circuit voltage, short-circuit loss, and zero-sequence impedance of various types of transformers. It can automatically perform waveform distortion correction, temperature correction, voltage correction (no-load test under non-rated voltage), and current correction (short-circuit test under non-rated current). The operator only needs to input the correction index based on the transformer type, and the instrument will automatically calculate the corrected results. It allows external voltage and current transformers to expand the measurement range, enabling measurement of test objects with any parameters.



The Transformer Capacity Characteristic Tester is specifically designed for testing the capacity of standard distribution power transformers under low voltage and low current conditions. Its built-in test power supply can complete capacity tests for 100 units of 2500KVA distribution transformers on a single charge. It adopts advanced A/D synchronous AC sampling technology and digital signal processing technology, with exquisite circuit design, unique concepts, superior performance, powerful functions, small size, and light weight. It adopts an integrated design for easy portability and field operations, fully meeting the requirements for on-site distribution transformer capacity testing. It features Chinese character display and prints measurement data of interest to users.



2 Design Purpose

China's power system implements a two-part tariff: in addition to the fees charged by metering devices, a basic electricity fee is also charged based on transformer capacity; for larger users, a one-time capacity increase fee is required when commissioning transformers. With the development of the power industry and the increase in electricity consumption, self-owned transformers and privately contracted transformers have gradually occupied a considerable share of distribution transformers. Consequently, individuals have resorted to various fraudulent means (mainly altering or replacing transformer nameplates) to reduce fees and increase electricity usage; some users steal electricity fees amounting to hundreds of thousands of yuan annually, and power departments lack effective control measures. The Transformer Characteristic-Capacity Comprehensive Tester is a high-precision instrument specifically developed by the company to address this issue, designed for measuring transformer capacity and loss parameters.



3 Usage Features

The Transformer Capacity Characteristic Tester comes with a high-efficiency rechargeable battery, allowing operation without external power supply. A single charge can support continuous measurements of dozens to hundreds of units. Additionally, it internally synthesizes a three-phase standard sine wave signal (not a simple inverter AC output, ensuring accurate test data for various test items under non-rated conditions), and through a power amplifier, it provides a three-phase precision AC test source. When measuring transformer capacity and short-circuit loss, no external three-phase test power supply, voltage regulator, or current booster is needed, simplifying wiring and greatly improving work efficiency. The capacity test accuracy rate reaches 100%. It is equivalent to two devices in one: an active transformer capacity tester plus a transformer loss parameter tester. It can precisely measure a series of power frequency parameters such as capacity, no-load current, no-load loss, short-circuit loss, and impedance voltage for various transformers. The Transformer Capacity Characteristic Tester has advantages such as small size, light weight, high measurement accuracy, good stability, and easy operation, fully replacing previous multi-meter methods for measuring transformer loss and capacity. It features simple wiring, convenient testing and recording, and greatly improves work efficiency. The Transformer Capacity Characteristic Tester uses a large-screen graphical LCD as the display window, with graphical menu operation and Chinese prompts, integrating multiple parameters on one screen. The human-machine interface is friendly, easy to use, and fast, making it the preferred product for power users at all levels.



4 Features

1. Can accurately measure the capacity of various distribution transformers with passive measurement, convenient and accurate.



2. Built-in power supply automatically generates a three-phase high-power test power source.



3. Can measure no-load current, no-load loss, short-circuit voltage, and short-circuit loss of various types of transformers.



4. Can automatically perform waveform distortion correction, temperature correction, voltage correction, and current correction (short-circuit test under non-rated current). The operator only needs to input the correction index based on the transformer type, and the instrument will automatically calculate the corrected results, making it very suitable for units that do not have conditions for short-circuit tests on slightly larger capacity transformers.



5. Wide voltage range: maximum voltage measurement up to 750V, ensuring accuracy without switching gears. It will not damage the instrument due to incorrect gear selection.



6. Battery remaining percentage indication function, not just a simple low battery alarm.



6. Large-screen, high-brightness LCD display, full Chinese menu and operation prompts for a friendly human-machine dialogue. Touch buttons make operation easier, and the wide-temperature LCD with brightness adjustment adapts to all seasons.



7. Users can print test data at any time through the micro printer.



8. Test result storage function, capable of storing 200 sets of capacity test data.