The lightning protection element tester is an instrument suitable for testing the DC parameters of overvoltage protection components such as zinc oxide arresters (zinc

It has functions such as memory, calculation, hold, self-check, and leakage alarm. It features high-voltage short-circuit protection, overcurrent protection, and high-voltage presetting. The high-voltage self-discharge time is less than 5 seconds. The test results are displayed on two 3 1/2 LCD digital displays, one showing the voltage value and the other showing the current value, with high accuracy and good reliability. It can also serve as an adjustable DC high-voltage source (1kV to 10kV) with output current ≤1mA.

oxide valve plates and varistors) DC parameters.

Technical Parameters

Withstand voltage: AC 2.3kV 50Hz 1min

Operating temperature and humidity: 0℃~+40℃ <90%RH

Storage temperature and humidity: -10℃~+50℃ <90%RH

Power supply: AC220V±10% 50Hz

Power consumption: <40W

Dimensions: 280mm(L)×280mm(W)×90mm(D)

Weight: ≤4 kg

Main features of the lightning protection element tester:

(1) Suitable for testing DC parameters of overvoltage protection components such as zinc oxide arresters (varistors), metal-ceramic two-electrode and three-electrode discharge tubes, and vacuum lightning arresters.

(2) Features high-voltage short-circuit protection, overcurrent protection, high-voltage presetting, and range adjustment.

(3) Has self-check and discrimination functions, and can issue an audible alarm for over-range tests during measurement.

(4) Has memory, calculation, hold, control, and continuous testing functions.

(5) Test results are displayed on a 3 1/2-digit LCD, automatically showing accurate and reliable required data.

Technical specifications of the lightning protection element tester:

(1) Varistor measurement
Technical Specification Measurement Range Working Error Test Condition
Initial action voltage U1mA 0~1999V ≤±1%±1d 1mA±5μA
Leakage current I0.75U1mA 0~199.9μA ≤±2μA±1d 0.75U1mA
≤±1%±1d

(2) Discharge tube measurement

Technical Specification Measurement Range Working Error Test Condition
DC breakdown voltage Vsdc 8~1999V ≤±1%±1d Voltage rise rate
100V/S±10%

(3) Other specifications

Insulation resistance: ≥10MΩ (500V)

Withstand voltage: AC 2kV 50HZ 1min

Operating temperature and humidity: -5℃~+40℃ ≤85%RH

Storage temperature and humidity: -10℃~+50℃ ≤85%RH

Power supply: AC 110V/220V 50Hz/60Hz

DC 12V 0.5A

Power consumption: 10W