Inherent opening (closing) time

            Opening (closing) phase-to-phase difference

            Opening (closing) phase-to-phase difference

            Closing (opening) bounce time (bounce count)

            Test range: 0.01ms~10000ms

            Accuracy: 0.1%±2 digits within 1ms~100ms, 0.5%±2 digits for greater than 100ms

  2. Speed measurement: Just opening (just closing) speed

            Average speed over specified time period (stroke segment or angle segment)

            Speed measurement range: 1mm sensor 0.01~25.00m/s,

            0.1mm sensor 0.001~2.50m/s, 360° angle sensor 0.01~25.00m/s,  universal sensor: 0.01~10.00m/s

  3. Stroke measurement: Moving contact stroke (stroke)   Contact stroke (opening distance)  Over-travel or return stroke (over-travel)

  4. Sensor measurement range:

            Linear displacement sensor 50mm, resolution: 0.1mm, stroke 0.1~50mm

            Linear displacement sensor 300mm, resolution: 0.1mm, stroke 10~300mm (optional)

            Linear displacement sensor 500mm, resolution: 1mm, stroke 10~500mm (optional)

            360-line sensor: 360o, resolution: 0.25o, stroke 1mm~1000mm     

  5.  Current measurement: Displayed current is the maximum current value of the opening (closing) coil

  6. Display: 320×240 LCD screen, contrast adjustable

  7. Data storage: Can store 100 sets of measurement data

  8. Printer: High-speed thermal printer

  9. Instrument power supply: AC/DC 220V ± 10%; 50Hz ± 2%

  10. DC power supply: Output voltage: 25~265V continuously adjustable, output current: ≤ 20A (short time)

  11. Main unit dimensions: 360×250×140mm

  12. Operating environment:  -10℃~+50℃

  13. Relative humidity: ≤90%