1The DF6000 variable frequency anti-interference dielectric loss tester is a high-precision testing instrument used in power plants, substations, and other field or laboratory settings to measure the dielectric loss tangent and capacitance of various high-voltage power equipment. The instrument features an integrated structure, incorporating a dielectric loss test bridge, a variable frequency voltage regulating power supply, a step-up transformer, and an SF6 high-stability standard capacitor. The high-voltage source for testing is generated by the internal inverter and stepped up by the transformer for testing the test object. The frequency can be varied to 45Hz or 55Hz, 55Hz or 65Hz, using digital notch technology to avoid interference from power frequency electric fields, fundamentally solving the problem of accurate measurement under strong electric field interference. It is also suitable for testing with generator power supply after a complete power outage. The instrument can be equipped with an insulating oil cup to test the dielectric loss of insulating oil. Usage conditions: -15℃∽40℃ RH<80%
2. Anti-interference principle: variable frequency method
3. Power supply: AC 220V±10%, frequency unrestricted
4. High voltage output: 0.5KV∽10KV, in 1kV increments
5. Accuracy: 2%
6. Maximum current: 200mA
7. Capacity: 1500VA
8. Self-excitation power supply: AC 0V∽50V, 45HZ/55HZ
9. Maximum current: 15A
10. Resolution: tgδ: 0.001%, Cx: 0.01pF
11. Accuracy: △tgδ: ±(reading*1.0%+0.040%), △Cx: ±(reading*1.0%+1.0PF)
12. Measurement range: tgδ unlimited, Cx 15pF<Cx<300nF (10KV), Cx<40nF (5KV), Cx<150nF (1KV), Cx<300nF, CVT test Cx<300nF
13. Dimensions: 430(L)×330(W)×330(H)
14. Memory capacity: 80 groups
15. Weight: 28 Kg